What is the largest branch breaker that can be mounted across from a QOB2150VH, QOB3150VH, QOB3125VH, or QOB3110VH breaker in NQOD or NQ Panelboards?
Issue:
What is the highest ampere branch breaker that can be mounted across from a QOB2150VH, QOB3150VH, QOB3125VH, or QOB3110VH breaker in NQOD or NQ Panelboards?

Product Line:
NQ/NQOD Panelboard

Environment:
Breaker placement restrictions

Cause:
Maximum amperage allowed

Resolution:
A 20A adjacent breaker is the largest branch breaker that can be mounted across from these breakers in a NQOD Panel.
A 40A adjacent branch breaker is the largest branch breaker allowed to be mounted across from the QOB 110A-150A VH breakers in a NQ Panel.