Do the QOM1 and QOM2 main breaker kits require any pole spaces when installed on a convertible, QO or Homeline main lug load center interior?
Issue:
Does the QOM main breakers require pole spaces when installed on a convertible main lug load center interior?
Product Line:
QO and Homeline load centers
Resolution:
No, the main circuit breaker kits do NOT require any pole spaces. They are NOT a branch mounted device and do not require branch circuit breaker mounting spaces.
Does the QOM main breakers require pole spaces when installed on a convertible main lug load center interior?
Product Line:
QO and Homeline load centers
Resolution:
No, the main circuit breaker kits do NOT require any pole spaces. They are NOT a branch mounted device and do not require branch circuit breaker mounting spaces.