How can we help you today?

What is the retaining kit for back feeding a branch breaker as a main in an NF panelboard?

Issue:
Retaining kit for backfed main breaker in NF panelboard?

Product Line:
NF panelboards

Environment:
Products sold in North America

Cause:
Back feeding main breaker

Resolution:
A retaining kit is not available or required when using a bolt in back fed main breaker.  The backfed main breaker should be clearly labeled as the Mains.

Schneider Electric Canada

Explore more
Range:
Category:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
Category:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and en expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings