How can we help you today?

What is the reset time for LRD thermal overload relay?

Unlike the LR9D solid state devices which have a specified automatic reset time, our LRD overloads are an electromechanical product and even when set on automatic reset we do not have reset time to provide.

The resetting time ( regardless of the specific product reference ) depends on :

- The kind of tripping ( IE: Thermal tripping, phase tripping, differential…. )

- The state of the overload ( IE: cold state, hot state )

- The ambient temperature

Combining all of these conditions leads to a variable time range before the reset can occur.

- The reset is allowed only when the internal bimetal sensors of the LRD** have come back to a position allowing reset.

- The bimetal sensor represents motor temperature and we need to cool down the motor prior to allowing a reset.

Schneider Electric Canada

Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and en expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings