How can we help you today?

TCSEGDB23F24FA - The value shown for the 'Total Error Count' does not match the summation of the Cable A and Cable B errors.

The value shown for the 'Total Error Count' does not match the summation of the Cable A and Cable B errors.
rfwf

If you run MBPStat and look at the 'Network Statistics' page, there is a status counter for “No response received”  (See below) which is an indication of that MB+ device trying to talk to another device not on the network to see if it has been added to the network.  This is what allows new devices to be added to the token ring passing algorithm and start communicating on the network.  The 'Total Error Count' would include the errors from both cable A and B plus the number of 'No responses received'.

ert

Schneider Electric Canada

Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings