What happens to Feature 2B (Time Delay Normal to Emergency N>E) and Feature 3A (Time Delay Retransfer to Normal E>N) if Feature 34A or 34B (Inhibit transfer) inputs are active in a Group 5 controller?

Feature 34A - Opening of the contact will prohibit transferring to the normal source
Feature 34B - Opening of the contact will prohibit transferring to the emergency source

Below are the simulations that were done to observe the operation of Feature 2B & Feature 3A when Feature 34 inhibit inputs are active.

TRANSFER NORMAL TO EMERGENCY

  • When 34B Contact Closed > Initiate Transfer N>E > TD N>E Countdown Running > Open Contact 34B > TD N>E Countdown Still Running > After Countdown Transfer Inhibited
  • -When 34B Contact Open > Initiate Transfer N>E > TD N>E No Countdown > Transfer Inhibited
TRANSFER EMERGENCY TO NORMAL
  • When 34A Contact Closed > Initiate Transfer E>N > TD E>N Countdown Running > Open Contact 34A > TD E>N Countdown Still Running > After Countdown Transfer Inhibited
  • When 34A Contact Open > Initiate Transfer E>N > TD E>N Countdown Running > After Countdown Transfer Inhibited
  • When 34A Contact Open > Initiate Transfer E>N > TD E>N Countdown Running > Close Contact 34A > Switch successfully retransfer to Normal

Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and en expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings