Why is the MOD_FLT of x80 DI/DO modules different between the local rack and the EIO rack?

In an M580 application, the device DDT associated with an X80 DI/DO module includes the MOD_FLT word.

For modules installed in an Ethernet RIO rack, background exchanges between the M580 CPU and the BMxCRA312x0 adapter update the device DDT.

The MOD_FLT information is not available for modules installed in the M580 local rack, including when using the READ_STS_MX EFB. This limitation is related to the M580 architecture.

To retrieve MOD_FLT for a module in an Ethernet RIO rack:

1- Enable Allow dynamic arrays (ANY_ARRAY_XXX) in EcoStruxure Control Expert:

  • For M580 Safety: Tools > Project Settings > Scope: Process > Variables
  • Standard M580: Tools > Project Settings > Variables

2- Create a section using the READ_STS_MX and ADDMX EFBs

3- Configure ADDMX with the IP address of the corresponding BMxCRA312x0 adapter

img1

For more information, see page 306 of the "Modicon X80 Discrete Input/Output Modules User Manual".

Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings
  • Preference Center