PO2021 Profile Studio equipment CSV import cause Standby IO Server doesn't exist error
Issue
PO2021 Profile Studio equipment CSV import cause Standby IO Server doesn't exist error
image.png
Product Line
PO2021
Environment
PSO/PO using Profile Studio to create Equipment package
Solution
There are two ways to solve this....
  1. Delete the content of Standby IO Server Name column or configure correct IO Server name in equipment.csv file. and save it.
image.png
  1. Make sure the package received from EPAS-E contains only one OIS HMI and not multiple HMI as below.
image.png

Schneider Electric Canada

Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:

Need help?

  • Product Selector

    Quickly and easily find the right products and accessories for your applications.

  • Get a Quote

    Start your sales inquiry online and en expert will connect with you.

  • Where to buy?

    Easily find the nearest Schneider Electric distributor in your location.

  • Help Center

    Find support resources for all your needs, in one place.

  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Register Your Product
  • Blog
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings