How can we help you today?

Do M580 Safety I/O MUIDs need to be re-generated after a Hot Swap?

Issue

If an M580S V3.20 has a Safety program currently running, does it require that the MUIDs be generated if a single module is damaged and needs to be replaced on the fly?

Product Line

Modicon M580 Safety

Resolution

The MUIDs are generated offline strictly by what is mapped in the particular slot. It does not use anything specifically from the actual module hardware for generation.

You can Hot Swap IO modules without impacting the application at all.

Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and en expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings