What will cause R1, R2 or R3 to open when programmed for "Operating state fault" on ATV630/ATV930?
Resolution:
If R1, R2, or R3 is assigned to "Operating State Fault", the relay remains active only when the drive status is RDY.
For any other drive status, including Run, Fault, or NST, the relay returns to its normal state.
This applies to both Local and Remote modes.
For information on how to program the Relays on the Altivar Process Drives please visit the FAQ FA245321 ( https://www.se.com/us/en/faqs/FA245321/ )