How can we help you today?

What can cause an SLF2 error on the ATV630 and ATV930 Drives?

Issue:

SLF2 error on the ATV600 and ATV900 process drives.

Product Line:

ATV600 and ATV900 process drives.

Environment:

All

Cause:

Communications fault with Somove

Resolution:

Check the connection to the Somove Software

Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings