What would cause the ATV320 series Drive to still trip on OBF if the DB resistor has been installed?

Issue:

ATV320 Drive is tripping on OBF after installing the DB resistor.

Product Line:

ATV320...... C version.

Environment:

All

Cause:

DC bus is still over charging on ramp down.

Resolution:

-Check to make sure the Jumper factory jumper is still installed between PO and PA+ ( C suffix version Drives only)

-Check to make sure the DB resistor is wired between PO and PB.

-Power down the drive, let the DC bus discharge then check the DB resistors value across PO and PB. (Drive needs to be powered OFF to do this test)

-Check the programming under FUN, rPt the bRA to make sure its set to NO.

-Verify the correct DB resistor size has been installed.

Schneider Electric Canada

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and en expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings