Video: How to sync time between a Machine Expert (EME) PLC and a Operator Terminal Expert (EOTE) HMI?


Issue:
Read the time information from the M241/M251/M262 PLC to synchronize the HMIST6 internal clock.

Product Line:
EcoStruxure Operator Terminal Expert, EcoStruxure Machine Expert

Resolution:
In order to synchronize the HMI time with the PLC time, you must make use of a few libraries in Machine Expert.

You will need to use the following:
SysTimeRtcGet -> This gets the controller's time
SysTimeRtcConvertUtcToDate -> This will convert the controller's UTC info to a readable date
SYSTIMEDATE -> This will store all the date and time information in tags that can be used by the HMI in Operator Terminal Expert.

For a complete setup of an example of how to get and set the PLC time, please see the example in the attached file.
Please download the project to an HMI to test it out. It does not work in simulation mode.

Schneider Electric Canada

Attachment(s)
M251_HMIST6_RTC_synchronization.zip [5.83 MB]
Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings