Can an XDSE SPD be connect to a branch breaker with an existing load?

Issue:

XDSE SPD connection to a branch breaker.

Product Line:

Surge Protection Devices

Environment:

XDSE Surgelogic SPD

Resolution:

"Since the current drawn by the XDSE device during normal operation is negligible, the XDSE device can be connected to a dedicated, separate branch circuit or connected to a suitable existing branch circuit."

page 7, XDSE User Guide 9501 07/2018

It can but they will have to use a breaker that accepts multiple conductors per lug and also has the wire range that complies with the wire range that XDSEs has which is stated on its handout (XDSE Handout), #8 to #10 AWG. This will assure that the wire leads of the SPD device are still protected.

Schneider Electric Canada

Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and en expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings