Can Type K cable be used with an ATV212 drive?

Resolution:
Type K cable is not recommended for use with the ATV212 because this cable type was not included in the product’s verification and validation testing.

Type K cable may use conductors as small as 30 AWG, which have a smaller cross-sectional area than the conductors evaluated during ATV212 testing. Because of the smaller conductor size, individual strands could be damaged or broken when the terminal is tightened to the specified torque.

The ATV212 was tested with the following conductor classifications:

  • Class 5 per IEC 60228
  • Class C per UL 486A

For this reason, the use of Type K cable cannot be recommended or guaranteed for safe operation. Use cable that meets the conductor specifications validated for the ATV212.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings