How can I prevent / inhibit the Series 7000 Bypass Transfer Switch from switching over to Emergency power?

There are several ways to go about this.
  1. Turn the Emergency power source off (If this cannot be done, please see #2 or #3).
  1. Turn the BYPASS handle to connect the bypass switch to the NORMAL source.
  1. If the Automatic Transfer Switch with Bypass and Isolation switch came with either one of these optional accessories, 30** or 34B, either one can be used to prevent the switch from connecting to the Emergency source.

Acc 30A
Acc 30B
Acc 34