How can we help you today?

Why are the REAL data type variables data not showing correctly in Vijeo Designer when communicating to a Unity Quantum PLC?


Issue:
REAL data type variables data not showing correctly in Vijeo Designer when communicating to a Unity Quantum PLC


Product Line:
Vijeo Designer, Quantum PLC


Resolution:
The REAL data type variables may not show correctly due to word order not set correctly in Vijeo Designer. When the HMI is communicating to an Unity Quantum PLC the double word order must be "High word first". To change the word order, expand the I/O manager in the navigator and double click on the equipment.

image3

Next, ensure that the Double Word word order is set to "High word first"
image4







Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and en expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings