How do you configure a Freewheel Stop (NST) on an ATV6000 Medium Voltage drive using Ethernet?
Resolution:
Configuration Steps
-
Assign a CMD Bit for Freewheel Stop
- The CMD word includes unused bits (Bit 11 to Bit 15) that can be assigned to specific functions.
- Assign one of these bits (for example, Bit 15) to the Freewheel Stop function (parameter C515).
-
Define the Freewheel Stop Logic
- When Bit 15 = 0, the drive triggers a Freewheel Stop (NST).
- This applies in both CiA 402 drive communication state and I/O profile mode.
-
Understand the Active-Low Behavior
- The Freewheel Stop input is active-low:
- 1 (ON) → Normal operation with ramp stop (as configured in the STT parameter)
- 0 (OFF) → Drive performs a Freewheel Stop (motor coasts to stop)
- The Freewheel Stop input is active-low:
-
Verify Operation
- Ensure the assigned bit is correctly mapped and controlled via Ethernet commands.
- Test both states (1 and 0) to confirm proper stopping behavior.
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)