How to change the MAST task Cyclic to Periodic in RemoteConnect and SCADAPack x70 device?

In Cyclic mode, the MAST task uses all available time. Sufficient time should be allowed for bursts of other activity on the SCADAPack x70 device. For this reason, Cyclic mode is not recommended.

To change MAST task from Cyclic to Periodic:
  • Open RemoteConnect software
  • Create new project for SCADAPack 474
  • In Configuration-SPx70 Controller>SCADAPack x70 logic, open SCADAPack x70 logic editor
  • Under Project>Programs>Tasks>MAST, right click on MAST and select properties
  • MAST's properties window should appear
  • Change the configuration from Cyclic to Periodic, then click the Apply button and then the OK button to save the changes.
Mast
  • Make sure to apply update and build logic after writing the logic program

Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and en expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings