How do I configure an ATV320 drive for mixed control using terminals and Modbus?

Resolution:

To set up the ATV320 for mixed control (Terminals + Modbus), follow these key steps:

  1. Configure the control mode

    • Set CHCF = SEP (Separate mode) to allow independent command and reference sources.
  2. Assign the command source

    • Set Cd1 = Terminals to control start/stop via terminal inputs.
  3. Set the speed reference source

    • Assign Ref1 = Modbus so the speed reference is received via Modbus communication.
  4. Configure terminal input

    • Set LI1 = Forward (2-wire control) for basic run command functionality. (This is a default value)

This configuration enables:

  • Start/stop control through terminal wiring
  • Speed reference control via Modbus communication

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings