Issue:
Meaning of the indicator lights on HOM250PSPD and QO250PSPD Surgebreakers?
Products:
Internally Mounted Surge Protective Devices, Surgebreakers
Cause:
Hard to decipher the label representation of the indicator lights.
Resolution:
If the indicator light is ON it means that it is in Normal Operation
If the indicator light is OFF, need to check connections. Verify the line voltage at the point of connection; if all correct, replace QO250PSPD or HOM250PSPD.
Released for: Schneider Electric Canada