{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
Search FAQs
How to fix the “Context file no found on device” error in Tesys Island?
Issue:
Context file not found error in SoMove

Product Line:
Motor Management system Tesys Island

Environment:
IEC Contactors and Starters

Resolution:
The “Context file no found on the device” error is shown if the DTM connects to a bus coupler that has never been configured. In that case only a very limited functionality is available (diagnostic view only).
To fix this error user must disconnect from the device and exit back to the home screen of SoMove and configure a new project offline (Create a Project OFF-line). Once that project is created with avatars and an IP address for the bus coupler, select Store to Device and connect back to the Tesys Island to configure it.

Schneider Electric Canada

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: