Can a QOB-VH or QHB breaker be used in an NQOB panel?

Product Line:
Obsolete NQOB Panelboards

Resolution:
The NQOB panelboard originally took a Q1B branch breaker and was replaced by NQ with QO/QOB branch breaker.

The QOB-VH and QHB breakers did not exist during the life of the NQOB interior and, as a result, were never UL/CSA tested or approved for use in the panel. They are not designed to be installed in the NQOB interior.
Additionally, 100 A QOB breakers are the maximum branch breakers that can be added to an NQOB panelboard. If not already installed, an SK5668 branch connector kit will also be required.

Schneider Electric Canada