Can I-line panel be used on 240V open delta system?

Issue:

Can I-line panel be used on 240V open delta ?

Product Line:

I-line panelboard

Answer:

For I-line panelboard, using it in 240V open delta will not be an issue. There will be no restrictions as long as phase to phase voltage is 240V on all 3 phases and no neutral can be used.