Is a DC trip curve available for LA/LH type circuit breakers?
Product Line:
Circuit Breakers
Resolution:
Thermal magnetic circuit breakers on DC systems retain their thermal tripping characteristics (same value as Vac). But for the magnetic part, a multiplier must be applied to the AC magnetic level to determine an equivalent DC trip level.
Multiplier on Magnetic Settings for LA/LH:
Hi Setting = 1.2
Lo Setting = 1.3
There is no trip curve showing this altered magnetic trip level for DC systems.