Why is the bottom of a Low Voltage Dry type transformer would need to be left open when mounted in the ceiling?
Issue:
EX225T65H is mounted from the ceiling and the bottom is wide open. is there a reason that this would need to be left open like this?
Product Line:
Low Voltage Dry Type Transformers
Environment:
EX/EXN and EE transformers
Cause:
Product features clarification
Resolution:
The bottom of a transformer is open when mounted in the ceiling to allow proper evacuation of the heated air from the core/coil.
Transformers rated 225KVA and above in the J-style enclosures are switchboard construction, which means open bottoms. There will not be any bottom plates or covers.
SquareD/Schneider Electric does not offer any type of bottom plates or covers as accessory components.
Released for: Schneider Electric Canada