When is a 3-point latch system required in a panelboard?

Issue:

A customer wanted to know if we can use NC74VS, instead of NC74VS3PNF in panels. Is there any reason why the L-frame needs the 3-point latch?


Product Line:

NQ/NF Panelboards


Environment:

Application


Cause:

Product Features


Resolution:


The PowerPact L frame main breaker interior requires the trim with the 3-point latch to meet the short circuit testing.

The vented trims with the 3-point latch vault handle are required when the main breaker is a PowerPact L frame.\

If you are using an L-frame Main breaker. You can't use the standard trim it has to be a 3-point latch


UL Short Circuit Testing dictates which locking system is required to meet their test criteria.

Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and en expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings