What are the VR Breaker Time Characteristics?

Issue:

VR Breaker Time Characteristics.

Product Line:

Metal Clad Switchgear.

Environment:

VR Breaker.

Cause:

Define VR Breaker Time Characteristics.

Resolution:

MAX. TIME FROM ENERGIZING TRIP COIL UNTIL:

Main Contacts Part31-36ms
Auxiliary Switch β€œA” Contacts Open 27-47ms
Auxiliary Switch β€œB” Contacts Close38-48ms

MAX. TIME FROM ENERGIZING CLOSING COIL UNTIL:

Main Contacts Complete The Closing35-75ms
Auxiliary Switch β€œA” Contacts Close38-86ms
Auxiliary Switch β€œB” Contacts Open 41-87ms

RATED INTERRUPTING TIME:

All Breakers50ms,   3.00 Cycles

PERMISSIBLE TRIPPING DELAY:2 Seconds

MAX. SPRING CHARGING TIME:10 Seconds max