GV2 Mounted side by side: Thermal setting

Issue:

Thermal trip setting for multiple GV2 units mounted side by side.

Product Line:

IEC Contactors and Starters

Environment:

Tesys GV2 Manual Starters

Resolution:

When several products GV2ME, GV2P or GV2RT are mounted side by side, the thermal trip setting Ir may need to be adjusted up to 1.1 x Ir.

Do not exceed the maximum thermal setting Ir.

Example: GV2ME14, thermal setting range: 6-10 A, do not adjust Ir above 10A.