IDP10-T Calibration at 0.00 Differential Pressure

Before beginning, make sure 0.00 D/P is applied to transmitter

  1. Press NEXT 3 times and CALIB will be displayed.
  2. Press ENTER and CAL AT0 will be displayed.
  3. Press ENTER and transmitter will display CALWAIT.
  4. Wait until transmitter displays AT0done
  5. Press NEXT 7 times and SAVE will be displayed.
  6. Press ENTER and transmitter should return to measurement mode indicating 0.00.
  7. Complete