How can we help you today?

Error 1720 gets returned when trying to install a new version of Control Expert on top of an older version.

The following error gets returned when trying to install a newer version of Control Expert on top of an older version.

Error 1720. There is a problem with this Windows Installer package. A script required for this install to complete could not be run. Contact your support personnel or package vendor. Custom action UP_TopologyManager_Service_Check script error -2146828275, Microsoft VBScript runtime error: Type mismatch: 'Session.Property' Line 25, Column 2,

To resolve the issue,

  • Open the folder named 'C:\Program Files (x86)\Schneider Electric'
  • Delete the folder for the old version of Control Expert.
  • If the folder cannot be deleted, resolve the trusted access rights issue and retry.
  • If the folder still cannot be deleted, open the Control Expert folder and delete the contents.
  • Reboot the PC.
  • Mount the installation  iso file for the older Control Expert version.
  • Run setup as an administrator.
  • Select Repair.
  • Reboot the PC.
  • Mount the installation iso file for the older Control Expert version.
  • Run setup as an administrator.
  • Select Remove.
  • Reboot.
  • Install the newer version of Control Expert.

Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings