- Press the NEXT button twice and the word CONFIG will be displayed.
- Press ENTER and EX ZERO will be displayed
- Press NEXT 7 times and EGU LRV will be displayed
- Press ENTER and the current EGU LRV value will be displayed with a blinking cursor at the left side of the display.
- Press ENTER and the left hand most digit will flash.
- Press NEXT until this digit matches the value of the most significant digit of the desired LRVvalue then press ENTER. Repeat procedure for the remaining 3 digits until the entire LRVvalue has been entered
- Press ENTER and SET DP will be displayed
- Press NEXT until the decimal point is in the correct location
- Press ENTER and EGU URV will be displayed.
- Press NEXT 2 timesand SAVE will be displayed
- Press ENTER and device will be returned to Measurement Display
- Complete
Released for:Schneider Electric Canada
Discontinued
Discontinued
Discontinued
Discontinued