Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
How to downgrade firmware version of HDPM6000 v0.58.4 to v0.56, and release notes (Version 58)
Issue
User would like to downgrade the firmware version on the HDPM6000 Head Unit

Production Line
HDPM6000 Head Unit

Environment
HDPM6000 Head Unit Firmware downgrade and release notes

Cause
Customer needs to downgrade the HDPM6000 Firmware version v58 to v56

Resolution
It is not recommended to downgrade the firmware version of the HDPM6000 Head Unit.
See Release notes attached, pg 2.
Downgrading from the version 58 firmware bundle to the version 56 bundle will cause the head unit to lose accumulated energy on downgrade and also each time the meter is power cycled thereafter. Contact technical support if downgrading to the v56 firmware bundle is required and a workaround can be provided.

Schneider Electric Canada

Attachment(s)
HDPM Firmware v0.58.4 Release Notes_ZL0193-0C.pdf [534.96 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Register Your Product
  • Blog
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings