How can we help you today?

What does the Connection error bit indicate in the Modicon switch diagnostic DDT indicate?

Issue

Connection error bit indication


Product Line

Modicon Switch


Environment

EcoStruxure Control Expert


Resolution

The connection error is just monitoring the link status. If any port loses a link it will trigger the connection error. You can then look at the link status to see which port lost it's link.  You need to turn on the "Propagate connection error" in the switch configuration. It is under Diagnostics > Status Configuration > Device Status.

Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and en expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings