Naše značky

Vítejte na internetových stránkách společnosti Schneider Electric

Vítejte na našich internetových stránkách.
		
Jak vám dnes můžeme pomoci?
Is it possible replace a PRM without Control Expert?

Yes, it is possible.

In theControl Expert application, under PRM general settings, ensure the following options are checked and properly configured:

  • Create an entry for this device name in the DHCP server
  • Backup the PRM configuration in the FDR server on download

Once these settings are confirmed, follow these steps to correctly replace the PRM:

  1. Remove the PRM module to be replaced.
  2. Prepare the new PRM module:
    • Set its lower rotary switch to ‘E’ (Configuration file deletion) to clear any existing configuration.
    • Power up the new PRM and wait for the boot process to complete, then power it off.
  3. Match the rotary switch positions:
    • Check the rotary switch positions on the old PRM and set the new PRM identically.
  4. Install the new PRM:
    • Power up the new PRM in the same location as the old one.

The new PRM will boot and automatically retrieve its configuration file from the FDR server.

Schneider Electric Česká republika

Zjistěte více
Produkt:
Zjistěte více
Produkt:
  • Dokumentace k produktům
  • Software ke stažení
  • Nástroj pro výběr produktů
  • Hledání náhrady za produkty
  • Centrum nápovědy a kontakty
  • Najít naše pobočky
  • Získejte nabídku
  • Kde koupit
  • Komunita Schneider Electric
  • Kariéra
  • Profil společnosti
  • Nahlásit nevhodné chování
  • Přístupnost
  • Newsroom
  • Investoři
  • EcoStruxure
  • Vyhledávání pracovních míst
  • Blog
  • Zásady ochrany osobních údajů
  • Oznámení o souborech cookie
  • Podmínky použití
  • Změnit nastavení souborů cookie