Naše značky

Impact-Company-Logo-English Black-01-177x54

Vítejte na internetových stránkách společnosti Schneider Electric

Vítejte na našich internetových stránkách.
		
Jak vám dnes můžeme pomoci?
HMI P6 : How to solve the virtual disk service error after a write filter usage ?

The goal of this FaQ is to explain how to solve the 'virtual disk' service error after a write filter usage.

This issue can occur after a volume modification (like Shrink a new system volume).

The device impacted is the Harmony P6 IPC Box.

Procedure steps

  1. Open the Windows task manager.
  2. Reach the ‘services’ tab
  3. Click on ‘Open Services’ tab
    Task Manager
  4. Open ‘Properties’ of ‘Optimize drives
  5. Change ‘Startup type’ from disable to ‘Automatic (Delayed Start)


Services

Shrink/Extend feature will work when you have finished the above processes.

Keywords HMIP6, Shrink volume, virtual disk, UWF, write filter
Author Lilian Cabos

Schneider Electric Česká republika

Zjistěte více
Produkt:
Řada:
Zjistěte více
Produkt:
Řada:
  • Dokumentace k produktům
  • Software ke stažení
  • Nástroj pro výběr produktů
  • Hledání náhrady za produkty
  • Centrum nápovědy a kontakty
  • Najít naše pobočky
  • Získejte nabídku
  • Kde koupit
  • Komunita Schneider Electric
  • Kariéra
  • Profil společnosti
  • Nahlásit nevhodné chování
  • Přístupnost
  • Newsroom
  • Investoři
  • EcoStruxure
  • Vyhledávání pracovních míst
  • Blog
  • Zásady ochrany osobních údajů
  • Oznámení o souborech cookie
  • Podmínky použití
  • Změnit nastavení souborů cookie