Tracking DB Lock Usage in Geo SCADA
DB Lock Usage could be tracked and historized. This is helpful to visualize the utilization of database locks across the system over time.
Several OPC properties related to DB Lock Usage are located here:
  • PerformanceStats.LUSPercLockAcquired
  • PerformanceStats.LUSPercLockAcquiredTime
  • PerformanceStats.LUSAlarmed

The LUSPercLockAcquired OPC property is the one we are interested in. Please create an Analog Calculation point and configure it to the following settings:
Calculation Point Settings
Calculation Point Settings
Make sure the Historic aggregate is enabled on the calculation point.
The DB Lock Usage can now be tracked:
Trending DB Lock Usage
Viewing DB Lock Usage in Historic List