Issue:
VW3A3721 Ethernet module on the ATS480 soft starters was triggering INF6?
Product Line:
ATS480
Environment:
All
Cause:
Soft starter was triggering INF6.
Resolution:
VW3A3721 card is not compatible with ATS480 it will trigger an INF6 error.
To use Ethernet with ATS480, you need to use the Ethernet cardVW3A3720, this card must have a firmware V2.1IE28 or greater.