Naše značky

Vítejte na internetových stránkách společnosti Schneider Electric

Vítejte na našich internetových stránkách.
		
Jak vám dnes můžeme pomoci?
Cannot open Control Expert after installing and it returns an Srcsdk.dll related error.

The reasons why Control Expert  cannot be opened and returns an Srcsdk.dll related error is due to some of the ISS Setup Prerequisites sub components not getting successfully installed.

The ucmerr.log file found in folder named 'C:\ProgramData\Schneider Electric\Control Expert 15.3' could show an error similar to :
ucm

The sub components are located in the folder named '...:\ISSetupPrerequisites'.

The issue can be resolved by performing the following steps:

  • Run a registry cleaner
  • Reboot.
  • Open\mount the Control Expert installation iso file.
  • Reinstall all of the sub components found in the folder named '....:\ISSetupPrerequisites'.
  • Reboot.
  • Retest.

preq

Schneider Electric Česká republika

Přílohy
RegClean.7z [255.84 KB]
Zjistěte více
Řada:
Zjistěte více
Řada:
  • Dokumentace k produktům
  • Software ke stažení
  • Nástroj pro výběr produktů
  • Hledání náhrady za produkty
  • Centrum nápovědy a kontakty
  • Najít naše pobočky
  • Získejte nabídku
  • Kde koupit
  • Komunita Schneider Electric
  • Kariéra
  • Profil společnosti
  • Nahlásit nevhodné chování
  • Přístupnost
  • Newsroom
  • Investoři
  • EcoStruxure
  • Vyhledávání pracovních míst
  • Blog
  • Zásady ochrany osobních údajů
  • Oznámení o souborech cookie
  • Podmínky použití
  • Změnit nastavení souborů cookie