Naše značky

Vítejte na internetových stránkách společnosti Schneider Electric

Vítejte na našich internetových stránkách.
		
Jak vám dnes můžeme pomoci?
PME all versions - Log Inserter won't open in Designer if a Log Acquisition Module (LAM) has too many inputs

Product Line:

Power Monitoring Expert all versions
_____________________________________________________________
Environment:

Designer

_____________________________________________________________
Issue :

Log Inserter won't open in Designer if a Log Acquisition Module (LAM) has too many inputs

In Designer, you will see a 'communications error' dialog. In the system log you will see this error:
Image
_____________________________________________________________
Proposed Solution:
There is a certain limitation on the number of inputs can be connected to a Log Acquisition Module. Try to reduce the number of inputs to below 1500 per Log Acquisition Module. Add a second Log Acquisition Module if further inputs are required.

Schneider Electric Česká republika

Zjistěte více
Produkt:
Zjistěte více
Produkt:
  • Dokumentace k produktům
  • Software ke stažení
  • Nástroj pro výběr produktů
  • Hledání náhrady za produkty
  • Centrum nápovědy a kontakty
  • Najít naše pobočky
  • Získejte nabídku
  • Kde koupit
  • Komunita Schneider Electric
  • Kariéra
  • Profil společnosti
  • Nahlásit nevhodné chování
  • Přístupnost
  • Newsroom
  • Investoři
  • EcoStruxure
  • Vyhledávání pracovních míst
  • Blog
  • Zásady ochrany osobních údajů
  • Oznámení o souborech cookie
  • Podmínky použití
  • Změnit nastavení souborů cookie