Humidification Strategies for Data Centers and Network Rooms

The control of humidity in Information Technology environments is essential to achieving high availability. This paper explains how humidity affects equipment and why humidity control is required. Quantitative design guidelines for existing and new computing installations are discussed. Alternative methods to achieve desired humidity are described and contrasted. The difficult issue of how and where humidity should be measured is explained. The hidden costs associated with over-humidification are described.

Dato: 23 januar 2015 | Skriv: White paper
Sprog: Engelsk | Version: V3
Dokument reference: SPD_NRAN-5TV85S_EN