How do I configure my ATV212 series drive for Apogee communication?
Issue:
Configuring ATV212 series drive for Apogee communication.
Product Line:
ATV212 series drives
Environment:
All models where Apogee communication is in use.
Cause:
Information unclear in current literature.
Resolution:
Basic parameters are as follows:
F807 - Com channel choice - 0 for RJ45 port, 1 for 4 pin terminal block.
F829 - Network protocol, Set to 3 for Apogee (1- Modbus, 2-Metasys, 4-Bacnet *5-Lonworks. Note that an option card is necessary for Lonworks communication. All other options are built into the default control card of the drive)
F890 - Network Address (1 to 99)
F891 - Baud rate (0-9600, 1=4800, 2=9600, 3=19200, 4=76800, 5=57600, 6=76800)
F892 - Network timeout in 10ths. of a second. set to 100 (10.0 seconds) default. Range = 2 to 60 seconds.
The above settings are for monitoring only. If you wish to control via the Apogee network you must also make the following changes:
CMOD = 2 (switches start/stop control to the network. 0 = logic inputs, 1 = HMI, 2 = Serial communication).
FMOD = 4 (switches frequency reference to the network. 1 = VIA, 2 = VIB, 3 = Keypad, 4 = Serial communication, 5 = +/- speed via logic input.
Configuring ATV212 series drive for Apogee communication.
Product Line:
ATV212 series drives
Environment:
All models where Apogee communication is in use.
Cause:
Information unclear in current literature.
Resolution:
Basic parameters are as follows:
F807 - Com channel choice - 0 for RJ45 port, 1 for 4 pin terminal block.
F829 - Network protocol, Set to 3 for Apogee (1- Modbus, 2-Metasys, 4-Bacnet *5-Lonworks. Note that an option card is necessary for Lonworks communication. All other options are built into the default control card of the drive)
F890 - Network Address (1 to 99)
F891 - Baud rate (0-9600, 1=4800, 2=9600, 3=19200, 4=76800, 5=57600, 6=76800)
F892 - Network timeout in 10ths. of a second. set to 100 (10.0 seconds) default. Range = 2 to 60 seconds.
The above settings are for monitoring only. If you wish to control via the Apogee network you must also make the following changes:
CMOD = 2 (switches start/stop control to the network. 0 = logic inputs, 1 = HMI, 2 = Serial communication).
FMOD = 4 (switches frequency reference to the network. 1 = VIA, 2 = VIB, 3 = Keypad, 4 = Serial communication, 5 = +/- speed via logic input.
Udgivet til: Schneider Electric Danmark




Brug for hjælp?
Produktvælger
Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.
Få et tilbud
Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.
Find forhandler
Find den nærmeste Schneider Electric-distributør.
Hjælpecenter
Find supportressourcer til alle dine behov på ét sted.