How to correct error 22321 Liquid:Calculation of Density at base conditions unsuccessful in Realflo?

Scenario:
  • The scadapack is polling values from the Coriolis Meter.
  • When the Coriolis Meter losses connections or it stop communicating, The Realflo Run liquid will use the default setting parameters.
  • Make sure that correct parameters are entered on the Default value.
For example: If the default value for the Density was set to 1 when measuring Liquid and the Coriolis meter losses communications then
the flow computer will used the default value 1 to calculate the flow and will give an error result of 22321 "Liquid:Calculation of Density at base conditions unsuccessful"

Use the table below for Density default value:

Schneider Electric Danmark

Se mere
Område:
Se mere
Område:

Brug for hjælp?

Brug for hjælp?

Produktvælger

Produktvælger

Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.

Få et tilbud

Få et tilbud

Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.

Find forhandler

Find forhandler

Find den nærmeste Schneider Electric-distributør.

Hjælpecenter

Hjælpecenter

Find supportressourcer til alle dine behov på ét sted.

  • Produktdokumentation
  • Download af software
  • Produktvælger
  • Udskiftning og erstatning af produkter
  • Hjælp og kontaktcenter
  • Find forhandler
  • Projektrådgivning
  • Find vores kontorer
  • Schneider Electric Community
  • Karriere
  • Virksomhedsprofil
  • Rapportér en forseelse
  • Tilgængelighed
  • Presserum
  • Investorer
  • EcoStruxure
  • Jobsøgning
  • Blog
  • Privatlivspolitik
  • Cookiemeddelelse
  • Vilkår for anvendelse
  • Rediger dine cookieindstillinger