{}

Vores varemærker

Impact-Company-Logo-English Black-01-177x54

Velkommen til Schneider Electrics website

Velkommen til vores website
Hvordan kan vi hjælpe dig i dag?
How to Refresh an Embedded List in ClearSCADA?
Here are the steps to execute the automatic refresh on the embedded list:
  1. Right-click on the created embedded list and choose properties
  2. under "General" tab click "Pick Action"

  3. select "Script and press next

  4. select Mode "Execute Code Fragmentation on Top-Level Mimic" and write the code as follows Mimic.Layers(0).Item("Lst_2").Sql = Mimic.Layers(0).Item("Lst_2").Sql

  5. select Next then Finish.

    Once configured, save the mimic and put it into runtime mode. If you left-click on the list, the query will update and the list will refresh automatically with the newest results displayed.

Schneider Electric Danmark

Se mere
Område:
Artikler som kan være nyttige
Se mere
Område: