Hvordan kan vi hjælpe dig i dag?

Word order for RealFLO Modbus Registers in an x70 Controller

RealFLO Modbus registers require a word order of “High byte/High word first”.  When running a RealFLO flow computer in a SCADAPack x70 controller, the user must ensure that this is set correctly.
The following screen shots (from Remote Connect) show the proper settings for setting the RealFLO Modbus Registers word order.

1. Ensure that the ‘Realflo Flow Computer’ box is checked in the ‘Project Settings’ dialog








2. Ensure that the word order is set properly in the Modbus | Master/Client | FlowComputer dialog.  The correct setting is 'High byte/High word first'.








3. Ensure the word order is set properly in the Modus | SlaveServer dialog.  The correct setting is 'High byte/High word first'.









With the above settings in place, the modbus registers that contain the flow computer data will display the data correctly.

Schneider Electric Danmark

Brug for hjælp?

Brug for hjælp?

Produktvælger

Produktvælger

Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.

Få et tilbud

Få et tilbud

Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.

Find forhandler

Find forhandler

Find den nærmeste Schneider Electric-distributør.

Hjælpecenter

Hjælpecenter

Find supportressourcer til alle dine behov på ét sted.

  • Produktdokumentation
  • Download af software
  • Produktvælger
  • Udskiftning og erstatning af produkter
  • Hjælp og kontaktcenter
  • Find forhandler
  • Projektrådgivning
  • Find vores kontorer
  • Schneider Electric Community
  • Karriere
  • Virksomhedsprofil
  • Rapportér en forseelse
  • Tilgængelighed
  • Presserum
  • Investorer
  • EcoStruxure
  • Jobsøgning
  • Blog
  • Privatlivspolitik
  • Cookiemeddelelse
  • Vilkår for anvendelse
  • Rediger dine cookieindstillinger