Powerlogic P7 - No Voltage Display Using Open Delta PT Scheme and 52A signal Not Responding
Issue:
The customer reports that voltages are not displayed and the 52B input status is missing on the mimic panel.
Product:
PowerLogic P7 Relay
Environment:
Relay configured with an Open Delta PT scheme and local HMI mimic panel enabled.
Cause:
The mimic configuration was not properly updated to reflect the PT scheme and input status, causing the local HMI to show incomplete or incorrect data.
Resolution:
Update the mimic configuration to ensure the local HMI is properly animated. Below are the recommended settings and layout adjustments: