How to wire the built in analog input of the M221 to a Dwyer 626 pressure transmitter?

Issue
How to wire the built in analog input of the M221 to a Dwyer 626 pressure transmitter?

Product Line
SoMachine Basic / EcoStruxure Machine Expert-Basic, Modicon M221 PLC

Environment
Analog Input wiring

Resolution
The Dwyer 626 is a 3-wire connection which will requires it's own power supply.
The - (negative of M221) goes to the common and + (positive of M221) goes the white.  See below for more information:

Dwyer pressure transmitter:
Dwyer Pressure Transmitter pinout diagram
The receiver would be the M221 in this case.

M221 Analog Input +/-10V


For the types of wires required, also see the Modicon M221 Logic Controller User Guide
See Section 3.3 "Wiring Best Practices"
Document Link: https://www.se.com/ww/en/download/document/EIO0000000976/

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric Suomi

Lue lisää
Tuotesarja:
Lue lisää
Tuotesarja:
  • Tuotedokumentaatio
  • Ohjelmistolataukset
  • Tuotevalitsin
  • Tuotteen korvaaminen ja vaihtaminen
  • Asiakaspalvelukeskus
  • Etsi toimistomme
  • Pyydä tarjous
  • Osta täältä
  • Shop.se.com/fi/fi sulkeutuu
  • Schneider Electricin yhteisö
  • Uramahdollisuudet
  • Yritys
  • Ilmoita väärinkäytöksestä
  • Saavutettavuus
  • Newsroom
  • Sijoittajat
  • Tutustu EcoStruxure
  • Toimipisteet Suomessa
  • Löydä jälleenmyyjä
  • Avoimet työpaikat
  • Blogi
  • Tietosuojakäytäntö
  • Evästeilmoitus
  • Käyttöehdot
  • Muokkaa evästeasetuksia