Tuotemerkkimme

Impact-Company-Logo-English Black-01-177x54

Tervetuloa Schneider Electricin verkkosivustolle

Tervetuloa sivustollemme.
		
Kuinka voimme auttaa sinua tänään?
What would cause an INF3 fault on the ATV630 drive after you have updated the MCB firmware from version 1.3 to version 1.5?

Article available in these languages: Espanja

Issue:
INF3 fault cause on the ATV630 drive after you have updated the MCB firmware from version 1.3 to version 1.5.

Product Line:
Altivar ATV630

Environment:
All

Cause:
Firmware was updated and now they are getting an INF3 fault.

Resolution:
If the Main control board had been flashed on a different size drive HP and voltage  and you put the MCB on another drive not matching that HP and voltage it will trigger a INF3 fault.

Fix:  Replace the MCB with a brand new MCB. If you need to flash the main control board make sure its flashed on the same HP and voltage as the drive its going to be used on.

Schneider Electric Suomi

Lue lisää
Tuotesarja:
Lue lisää
Tuotesarja:

Tarvitsetko apua?

  • Tuotevalitsin

    Valitse tarpeitasi vastaavat tuotteet ja lisävarusteet nopeasti ja helposti.

  • Pyydä tarjous

    Ota yhteyttä myyntilomakkeen kautta. Asiantuntijamme ovat sinuun yhteydessä.

  • Löydä lähin jälleenmyyjä

    Löydä helposti lähin jälleenmyyjä.

  • Asiakaspalvelukeskus

    Löydä tukiresurssit kaikkiin tarpeisiisi yhdestä paikasta.

  • Tuotedokumentaatio
  • Ohjelmistolataukset
  • Tuotevalitsin
  • Tuotteen korvaaminen ja vaihtaminen
  • Asiakaspalvelukeskus
  • Etsi toimistomme
  • Pyydä tarjous
  • Osta täältä
  • Shop.se.com/fi/fi sulkeutuu
  • Uramahdollisuudet
  • Yritys
  • Ilmoita väärinkäytöksestä
  • Saavutettavuus
  • Newsroom
  • Sijoittajat
  • Tutustu EcoStruxure
  • Toimipisteet Suomessa
  • Löydä jälleenmyyjä
  • Avoimet työpaikat
  • Blogi
  • Tietosuojakäytäntö
  • Evästeilmoitus
  • Käyttöehdot
  • Muokkaa evästeasetuksia