Issue:
What is the cause of ILF [Internal Link Error] fault on an Altivar Process Drive?
Product Line:
Altivar Process Drive (ATV630, ATV930, ATV650, ATV950, ATV660, ATV960, ATV680, ATV980)
Environment:
All serial numbers for Altivar Process Drive
Cause:
N/A
Resolution:
Cause
Communication interruption between option module and the drive.
Remedy
What is the cause of ILF [Internal Link Error] fault on an Altivar Process Drive?
Product Line:
Altivar Process Drive (ATV630, ATV930, ATV650, ATV950, ATV660, ATV960, ATV680, ATV980)
Environment:
All serial numbers for Altivar Process Drive
Cause:
N/A
Resolution:
Cause
Communication interruption between option module and the drive.
Remedy
- Verify connection to the proper slot
- Slot A
- Communication Modules (DeviceNet, Ethernet IP, Profibus, ProfiNet...)
- I/O & Relay Module
- Slot B
- Encoder Card (Analog, Digital, Resolver...)
- I/O & Relay Module
- Slot A
- Verify the environment (electromagnetic compatibility)
- If using Communication Module, check drives firmware version. (For most cases it should be at least V1.5IExx)
- Save configuration file on keypad, remove option module and do a factory reset. If fault disappears then it might be a bad option module.
- Replace the option module.
Julkaistu: Schneider Electric Suomi




Tarvitsetko apua?
Tuotevalitsin
Valitse tarpeitasi vastaavat tuotteet ja lisävarusteet nopeasti ja helposti.
Pyydä tarjous
Ota yhteyttä myyntilomakkeen kautta. Asiantuntijamme ovat sinuun yhteydessä.
Löydä lähin jälleenmyyjä
Löydä helposti lähin jälleenmyyjä.
Asiakaspalvelukeskus
Löydä tukiresurssit kaikkiin tarpeisiisi yhdestä paikasta.