What can cause a LCF (Line contactor failure) on the Altivar Process Drive ATV630 and ATV930?

Issue:
What is the fault code LCF on the ATV630 and ATV930 drives?

Product Line:
ATV630  ATV930

Environment:
All serial numbers

Cause:
Customer said the drive had a fault code LCF.

Resolution:
The fault takes place as soon as the line contactor is not closed after a defined time (LCT).
This function allows the line contactor to close and open depending on the start/stop command.
Check the line contactor and its' wiring.
Check parameter LCT (Mains Voltage.time out) under Complete setting -> Generic functions -> Mains contactor comm -> Mains V. time out.
If there is a timing issue, try to increase this value.
The Mains Voltage time out is factory set to 5s.

Schneider Electric Suomi

Lue lisää
Tuotesarja:
Lue lisää
Tuotesarja:

Tarvitsetko apua?

Tarvitsetko apua?

Tuotevalitsin

Tuotevalitsin

Valitse tarpeitasi vastaavat tuotteet ja lisävarusteet nopeasti ja helposti.

Pyydä tarjous

Pyydä tarjous

Ota yhteyttä myyntilomakkeen kautta. Asiantuntijamme ovat sinuun yhteydessä.

Löydä lähin jälleenmyyjä

Löydä lähin jälleenmyyjä

Löydä helposti lähin jälleenmyyjä.

Asiakaspalvelukeskus

Asiakaspalvelukeskus

Löydä tukiresurssit kaikkiin tarpeisiisi yhdestä paikasta.

  • Tuotedokumentaatio
  • Ohjelmistolataukset
  • Tuotevalitsin
  • Tuotteen korvaaminen ja vaihtaminen
  • Asiakaspalvelukeskus
  • Etsi toimistomme
  • Pyydä tarjous
  • Osta täältä
  • Shop.se.com/fi/fi sulkeutuu
  • Schneider Electricin yhteisö
  • Uramahdollisuudet
  • Yritys
  • Ilmoita väärinkäytöksestä
  • Saavutettavuus
  • Newsroom
  • Sijoittajat
  • Tutustu EcoStruxure
  • Toimipisteet Suomessa
  • Löydä jälleenmyyjä
  • Avoimet työpaikat
  • Blogi
  • Tietosuojakäytäntö
  • Evästeilmoitus
  • Käyttöehdot
  • Muokkaa evästeasetuksia